AWG to mm2 Converter

Convert between American Wire Gauge and metric cross-section area. Includes ampacity ratings and nearest IEC metric equivalents.

IEC 60228 Metric Sizes

Common IEC metric cross-sections and their nearest AWG equivalent.

IEC mm2Nearest AWGAWG mm2Difference
0.5200.518-3.5%
0.75180.823-8.9%
1171.0-3.8%
1.5151.6-9.1%
2.5132.6-4.6%
4114.2-4.1%
696.6-9.5%
10710.5-4.8%
16516.8-4.8%
25326.7-6.4%
35233.6+4.2%
501/0 (0)53.5-6.5%
702/0 (00)67.4+3.9%
953/0 (000)85.0+11.8%
1204/0 (0000)107.2+11.9%
1504/0 (0000)107.2+39.9%
1854/0 (0000)107.2+72.6%
2404/0 (0000)107.2+123.9%
3004/0 (0000)107.2+179.9%

Full AWG Reference Table

AWGmm2Diameter (mm)Ampacity (A)
4/0 (0000)107.211.684230
3/0 (000)85.010.404200
2/0 (00)67.49.266175
1/0 (0)53.58.251150
142.47.348130
233.66.544115
326.75.827100
421.25.18985
516.84.62175
613.34.11565
710.53.66555
88.43.26450
96.62.90640
105.32.58835
114.22.30530
123.32.05325
132.61.828--
142.11.62820
151.61.45--
161.31.291--
171.01.15--
180.8231.024--
190.6530.912--
200.5180.812--
210.4100.723--
220.3260.644--
230.2580.573--
240.2050.511--
250.1620.455--
260.1290.405--
270.1020.361--
280.0810.321--
290.0640.286--
300.0510.255--
310.0400.227--
320.0320.202--
330.0250.18--
340.0200.16--
350.0160.143--
360.0130.127--
370.0100.113--
380.007970.101--
390.006320.0897--
400.005010.0799--

Ampacity values are for single copper conductor in free air at 60C insulation rating per NEC Table 310.16 guidelines. Actual installation ampacity depends on conductor material, insulation type, ambient temperature, and installation method.

About this tool

Covers

  • AWG sizes from 4/0 (0000) through 40
  • Metric cross-section area (mm2) and diameter (mm)
  • Ampacity ratings for copper conductors at 60C
  • IEC 60228 standard metric sizes (0.5 to 300 mm2)
  • Nearest-match lookup for non-standard values
  • Bidirectional conversion (AWG to mm2 and mm2 to AWG)

Limitations

  • Ampacity values are for single copper conductors in free air at 60C, not for specific installation methods
  • Does not account for aluminum conductors (different ampacity)
  • Does not cover kcmil/MCM sizes above 4/0
  • Not a substitute for NEC or IEC installation sizing calculations